Warehouse type sprinkler is designed for the special applications such as high level storage systems. These type of sprinklers gives the more water with more less pressure. If the users do correct pressure adjustments for ESFR Sprinklers, users don’t need any other sprinkler use for the between shelf.
These models design for the protect the shelf breaks. But in using these sprinklers users have to attention for features of sprinklers. Heat detection, sprinkler cover case is important. If the water shield doesn’t use in that system, sprinkler can’t reach estimated heat and don’t activate it.
Application areas:
- Warehouses
- Big shops
- Stack storages
- Logistics
Warehouse type sprinkler, includes 4 models.
- ESFR (Early Suppression Fast Response) Sprinkler
- CMSA (Control Mode Specific Application) Sprinkler
- CMDA (Control Mode Density Area) Sprinkler
- EC Storage (Extended Coverage) Sprinkler
ESFR has 3 different with other sprinklers
Pendent
Connection diameter: ¾”npt
Assemble type: Pendent (Pendent) Tip
K-Factor: 14 (200)
Approvals: FM, UL, ULC, LPCB, VdS
Temperature: 74°C, 96°C
Surface: Brass
Sin: VK500
- ESFR (Early Suppression, Fast Response) in fire fighting mode
- With solder it strong against the heat.
- Design for the shelf systems protect.
- Suitable for using in shelf systems.
Connection diameter: ¾”npt
Assemble Type: Upright Type
K-Factor: 14 (200)
Approvals: FM, UL, ULC, LPCB, VdS
Temperature: 74°C, 96°C
Surface: Brass
Sin: VK520
- ESFR (Early Suppression, Fast Response) in fire fighting mode
- With solder it strong against the heat.
- Design for the shelf systems protect.
- Suitable for using in shelf systems.
- Solution for the instead of the pendent sprinkler connections.
Connection diameter: ¾”npt
Assemble type: Pendent type
K-Factor: 16.8 (242)
Approvals: FM, UL, ULC, LPCB, VdS
Temperature: 74°C, 96°C
Surface: Brass
Sin: VK503
- ESFR (Early Suppression, Fast Response) in fire fighting mode
- With solder it strong against the heat.
- Design for the shelf systems protect.
- Suitable for using in shelf systems.
- Instead of the ESFR K: 14 it needs low pressure than this sprinklers
Connection Diameter: 1”npt
Assemble type: Pendent type
K-Factor: 22.4 (320)
Approvals: FM, UL, ULC, LPCB, VdS
Temperature: 74°C, 96°C
Surface: Brass
Sin: VK506
- ESFR (Early Suppression, Fast Response) in fire extinction mode.
- With solder it strong against the heat.
- Design for the shelf systems protect.
- Suitable for using in shelf systems.
- Instead of ESFR K: 17, it needs low pressure
Connection diameter: 1”npt
Assemble type: Pendent type
K-Factor: 25 (363)
Approvals: FM, UL, ULC, LPCB, VdS
Temperature: 74°C, 96°C
Surface: Brass
Sin: VK510
- ESFR (Early Suppression, Fast Response) in fire extinction mode.
- With solder it strong against the heat.
- Design for the shelf systems protect.
- Suitable for using in shelf systems.
- Instead of ESFR K: 22, it needs low pressure
Connection dia: ½”npt – ¾”npt
Assemble type: Upright type
K-Factor: 11.2 (160)
Approvals: FM, UL, ULC
Temperature: 68°C, 93°C, 141°C
Surface: Brass
Sin: VK540
- With 5 mm bulb glass it is strong against heat.
- It design for until High Challenge Large Drop Sprinkler group A plastic fires extinction. For 7,6 meter height and 9,1 meter height it protect the shelf systems without any extra sprinklers.
- Between deflector and pallet of the top of the shelf have to be most least 914 mm.
Connection diameter: 1”npt
Assemble: Pendent type
K-Factor: 19.6 (282.6)
Approvals: FM, UL, ULC
Temperature: 71°C, 96°C
Surface: Brass
Sin: VK592
- With solder, it strong against the heat.
- It design for until Standart Response CMSA Pendent Sprinkler group A plastic fires extinction. For 7,6 meter height and 9,1 meter height it protect the shelf systems without any extra sprinklers.
- Between deflector and pallet of the top of the shelf have to be most least 914 mm.
Connection Diameter: ¾”npt
Assemble type: Upright type
K-Factor: 16.8 (242)
Approvals: FM, UL, ULC
Temperature: 68°C, 79°C, 93°C, 141°C
Surface: Brass
Sin: VK580
- With 5 mm bulb glass it is strong against heat.
- For needs low pressure, it makes low pipe line, lower pumps and it make some cost savings.
- Design for the high height storage systems
- Standard response sprinkler system.
Connection Type: ¾”npt
Assemble type: Upright / Pendent Type
K-Factor: 11.2 (160)
Approvals: FM, UL, ULC
Temperature: 68°C, 79°C, 93°C, 141°C
Surface: Brass, Chromed, Black and White
Sin: VK530 / VK536
- With 5 mm bulb glass it is strong against heat.
- Standard response sprinklers.
- With extra big orifice, design for the high capacitive storages and the manufacturers.
- For needs low pressure, it makes low pipe line, lower pumps and it make some cost savings
- If it use with the sprinkler cover case, it will be act like an intermediate level sprinklers.
Connection Type: ¾”npt
Assemble type: Upright / Pendent Type
K-Factor: 11.2 (160)
Approvals: FM, UL, ULC
Temperature: 68°C, 79°C, 93°C, 141°C
Surface: Brass, chromed, Black and White
Sin: VK531-533 / VK377
- With 3 mm bulb glass and, solder it strong against for the heat.
- Quick response sprinklers
- With extra big orifice, design for the high capacitive storages and the manufacturers.
- For needs low pressure, it makes low pipe line, lower pumps and it make some cost savings
- If it use with the sprinkler cover case, it will be act like a intermediate level sprinklers.
Connection Type: ½”npt
Assemble Type: Upright Type
K-Factor: 25.2 (363)
Approvals: FM, UL, ULC
Temperature: 74°C, 101°C
Surface: Brass
Sin: VK595
- With the solder, it strong against heat.
- Design for the high risky warehouses and productions.
- Between deflector and pallet of the top of the shelf have to be most least 914 mm.